3 Electrical Installation
- 72 -
In the preceding gure, the side entry copper busbar can be removed if necessary.
Terminal dimensions of main circuit terminals without the side entry copper busbar are
shown below.
.
4
3
5
6
7
8
Figure 3-34 Main circuit terminal dimensions of MD880-01S-0441-4/MD880-01S-0481-4
(without side entry copper busbar and output reactors)
Table 3-11 Main circuit cable selection for MD880-01S-0441-4-(L)/MD880-01S-0481-4-(L)
AC Drive
Model
Rated
Current
(A)
Recommended
Input/Output
Power Cable
(mm
2
)
Recommended
Lug Model
Recommended
Grounding
Cable (mm
2
)
Recommended
Grounding
Cable Lug
Model
Tightening
Torque
(N·m)
MD880-01S-
0441-4-(L)
441 2 x (3 x 95) BC95-12 95 BC95-12 35.0
MD880-01S-
0481-4-(L)
481 2 x (3 x 120) BC120-12 120 BC120-12 35.0
6
7
8
.
Figure 3-35 Main circuit terminal dimensions of MD880-01S-0538-4/MD880-01S-0605-4
(without output reactors)