3 Electrical Installation
- 74 -
Table 3-12 Main circuit cable selection for MD880-01S-0538-4-(L)/MD880-01S-0605-4-(L)
AC Drive
Model
Rated
Current
(A)
Recommended
Input/Output
Power Cable
(mm
2
)
Recommended
Lug Model
Recommended
Grounding
Cable (mm
2
)
Recommended
Grounding
Cable Lug
Model
Tightening
Torque
(N·m)
MD880-01S-
0538-4-(L)
538 2 x (3 x 120) BC120-12 120 BC120-12 35.0
MD880-01S-
0605-4-(L)
605 2 x (3 x 150) BC150-12 150 BC150-12 35.0
.
6
7
8
5
4
3
Figure 3-38 Main circuit terminal dimensions of MD880-01S-0673-4 to MD880-01S-0849-4
(without output reactors)