Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-108-
Detailed instruction of parameters
communication is not applied.
0: No check (N,8,1) for RTU
1: Even check (E,8,1) for RTU
2: Odd check (O,8,1) for RTU
3:No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check(O,8,2) for RTU
0~200ms
The interval time when the drive receives the data
and sends it to the upper computer. If the answer
delay is shorter than the system processing time,
then the answer delay time is the system processing
time; if the answer delay is longer than the system
processing time, then after the system deals with the
data, wait until achieving the answer delay time to
send the data to the upper computer.
Fault time of
communicatio
n overtime
0.0 (invalid), 0.1~60.0s
When the function code is set as 0.0, the
communication overtime parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications exceeds
the communication overtime, the system will report
“485 communication faults” (CE).
Generally, set it as invalid; set the parameter in the
continuous communication to monitor the
communication state.
Transmission
fault
processing
0: Alarm and stop freely
1: No alarm and continue to run
2: No alarm and stop according to the stop mode
(only under the communication control)
3: No alarm and stop according to the stop mode
(under all control modes)