Goodrive35 Series Closed-loop Vector Control VFD Basic operation instruction
150
Detailed instruction of parameters
7: Modbus communication setting torque (the
same as above)
8: PROFIBUS/CANopen communication
setting torque (the same as above)
9: Ethernet communication setting torque (the
same as above)
10: Reserved
-300.0%–300.0% (rated current of the motor)
Torque reference filter
time
Upper frequency of
forward rotation in
vector control
0: Keypad (P03.16)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDI (the same as above)
5: Multi-step (the same as above)
6: Modbus communication (the same as
above)
7: PROFIBUS/CANopen communication (the
same as above)
8: Ethernet communication (the same as
above)
Upper frequency of
reverse rotation in
vector control
0: Keypad (P03.17)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDI (the same as above)
5: Multi-step (the same as above)
6: Modbus communication (the same as
above)
7: PROFIBUS/CANopen communication (the
same as above)
8: Ethernet communication (the same as
above)
Keypad setting for
upper frequency of
forward rotation
0.00 Hz–P00.03 (max. output frequency)
0.00 Hz–P00.03 (max. output frequency)