Goodrive35 Series Closed-loop Vector Control VFD Basic operation instruction
170
S1
S2
S3
S4
S5
S6
S7
S8
HD1
P05.10
P05.01
P05.02
P05.03
P05.04
P05.05
P05.06
P05.07
P05.08
P05.09
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
P05.15
P05.17
P05.19
P05.21
P05.23
P05.25
P05.27
P05.29
P05.31
0
1
2
3
4
5
.
.
.
.
29
30
P05.11
(default value is 1)
(default value is 4)
(default value is 7)
(default value is 0)
(default value is 0)
(default value is 0)
(default value is 0)
(default value is 0)
(default value is 0)
P05.00
0
1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
P17.11
Switch input
terminal state
0 No function 1 Forward running
4 Forward jogging 5 Reverse jogging
8 Running pause 9 External fault input
12
Frequency increase/decrease
setting clear
13
Shifting between A frequency
and B frequency
16 Multi-stage speed terminal 1 17 Multi-stage speed terminal 2
20 Multi-stage speed pause 21 ACC/DEC time selection 1
2 Reverse running
6 Coast to stop
10
Frequency setting increasing
(UP)
14
Shifting between combination
setting and A frequency
18 Multi-stage speed terminal 3
22 ACC/DEC time selection 2
23 Simple PLC pause 25 PID control pause
28 Counter reset 29 Torque control disabling
26
Traverse pause (stop at the
current frequency)
30 ACC/DEC disabling
32 Length reset 33
Frequency increase/decrease
setting clear
34 DC braking
3 3-wire running control
7 Fault reset
11
Frequency setting decreasing
(DOWN)
15
Shifting between combination
setting and B frequency
19 Multi-stage speed terminal 4
23 Simple PLC stopping reset
27
Traverse reset (stop at the
middle frequency)
31 Counter trigging
35 Shift from motor 1 to motor 2
36
Shift the command to the
keypad
37
Shift the command to the
terminal
38
Shift the command to the
communication
39 Pre-exciting command
40 Power consumption clear 41 Power consumption keeping 42~63 Reserved
P07.37
The current
fault switch
input terminal
state
Fault?
S1 BIT0 S2 BIT1
S3 BIT2 S4 BIT3
S5 BIT4 S6 BIT5
S7 BIT6 S8 BIT7
HDI BIT8
P05.10, P17.11, P07.37 display
P05.00
0: HDI is high speed
pulse input
1: HDI is switch input
Fault
Switch function selection
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
T delay
P05.14
P05.16
P05.18
P05.20
P05.22
P05.24
P05.26
P05.28
P05.30
This parameter is used to set the function corresponds to the digital multi-function terminals.
Note: Two different multi-function terminals cannot be set as one function.
Set value
Function
Instructions
0
No function
The VFD does not work even there is input signal. It is
necessary to set the terminal which cannot be used to
non-function to avoid misacting.
1
Forward running (FWD)
The forward or reverse rotation of the VFD can be
controlled by the external terminals.
2
Reverse running (REV)
3
3-wire running control
The terminal can determine the running mode of the VFD
is 3-wire control mode. Refer to P05.13 for detailed
instruction of 3-wire control mode.
4
Forward jogging
See P08.06, P08.07 and P08.08 for jogging frequency,
and jogging ACC/DEC time.
5
Reverse jogging
6
Coast to stop
The VFD closes off the output. The motor is not controlled
by the VFD during the stopping. This method is usually to
be used when the load inertia is big and it has no
requirement to the stopping time.
It has the same meaning with the "coast to stop" in P01.08
and usually used in remote control.

Table of Contents