Goodrive35 Series Closed-loop Vector Control VFD Function parameters
75
Detailed instruction of parameters
communication, and the communication address is
0x200A.
Terminals control
running mode
This parameter is used to set the terminal-based
control mode.
0: 2-wire control mode 1, integrating the enabling
and direction setting functions. This is the most
common 2-wire mode. The forward or reverse
running of the motor is determined by the defined
FWD and REV terminals.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stop
Hold
on
Forward
running
Reverse
running
1: 2-wire control mode 2, separating the enabling
and direction setting functions. The defined FWD
terminal is used for enabling, and the direction is
determined by the defined REV terminal.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stop
Stop
Forward
running
Reverse
running
2: 3-wire control mode 1. In this mode, SIn is defined
as the enabling terminal, the running command is
determined by the FWD terminal, and the direction is
determined by the REV terminal. When the VFD is
running, terminal SIn must be in the connected state.
When terminal FWD generates a rising edge signal,
the VFD starts to run, and the running direction is
determined by terminal REV. To stop the running of
the VFD, you need to disconnect terminal SIn.