Inxpect SRE 200 Series| Instruction manual v1.5 DEC 2023 |Inxpect SAF-IM-200S_5m_7_00047_en_v1.5|© 2021-2023 Inxpect SpA
5. Safety functions
5.5.3 Precautions for preventing unexpected restarting
To prevent unexpected restarting, if the sensor is installed at a height of less than 15 cm (5.9 in) from the ground
to its center, a minimum distance of 50 cm (20 in) from the sensor must be guaranteed.
Note: if the sensor is installed at a height of less than 15 cm (5.9 in) from the ground to its center, an option is to
enable the masking function to generate a system error if a person stands in front of the sensor.
5.5.4 Configure the restart function
WARNING! If the Restart signal function has been enabled both through the safety Fieldbus and the
digital inputs, the functionality can be activated from both of them.
Type Procedure
Automatic 1. In the Inxpect Safety application in Settings > Restart function, select Automatic.
2. In the Inxpect Safety application, in Configuration for each detection field in use with
automatic restart, select the desired Safety working mode and set the Restart
timeout (or the T
OFF
parameter, if present).
Manual 1. In the Inxpect Safety application in Settings > Restart function, select Manual.
2. If there is a digital input configured as Restart signal (Settings > Digital Input-
Output), connect the machinery button for the restart signal as convenient (see
"Electrical connections" on page111).
3. To use the Fieldbus communication for the restart signal, make sure that no digital
input is configured as Restart signal (Settings > Digital Input-Output). See the
Fieldbus protocol for details.
4. In the Inxpect Safety application, in Configuration for each detection field in use with
manual restart, set the T
OFF
parameter value.
Note: the Safety working mode is automatically set to Always-on access detection for all
the detection fields in use with manual restart.
Safe manual 1. In the Inxpect Safety application in Settings > Restart function, select Safe manual.
2. If there is a digital input configured as Restart signal (Settings > Digital Input-
Output), connect the machinery button for the restart signal as convenient (see
"Electrical connections" on page111).
3. To use the Fieldbus communication for the restart signal, make sure that no digital
input is configured as Restart signal (Settings > Digital Input-Output). See the
Fieldbus protocol for details.
4. In the Inxpect Safety application, in Configuration for each detection field in use with
safe manual restart, select the Safety working mode among those allowed and set
the Restart timeout parameter value.