Inxpect SRE 200 Series| Instruction manual v1.5 DEC 2023 |Inxpect SAF-IM-200S_5m_7_00047_en_v1.5|© 2021-2023 Inxpect SpA
8. Installation and use procedures
8.4.2 Start the Inxpect Safety application
1. Connect the control unit to the computer using a data USB cable with a micro-USB connector or the Ethernet
cable (if an Ethernet port is available).
2. Supply power to the control unit.
3. Start the Inxpect Safety application.
4. Choose the connection mode (USB or Ethernet).
Note: the default IP address for the Ethernet connection is 192.168.0.20. The computer and the control unit
must be connected to the same network.
5. Set a new admin password, memorize it, and provide it only to authorized people.
6. Select the system Inxpect SRE 200 Series, the sensor model-type (5 meters range sensors or 9 meters range
sensors), and the number of sensors.
7. Optional. Reset and re-assign all Node IDs.
8. Set the country in which the system is installed.
Note: this setting does not have any effect on system performance or safety. The country selection is requested
during the first installation of the system to configure the system’s radio profile, which must comply with the
national regulations of the installation country.
9. Select the application type:
o
for stationary applications, select Stationary.
o
for installation on a machine moving gantry, on a truck on rails, on a crane, select Mobile.
o
for both automated guided vehicles and vehicles with driver, select Vehicle.
Note: the algorithms are optimized to minimize the interference between sensors based on the installation
conditions. Even though this choice does not affect the performance and the robustness, it is mandatory to
select the correct application type.
8.4.3 Define the area to be monitored
WARNING! The system is disabled during configuration. Prepare opportune safety measures in the
dangerous area protected by the system before configuring the system.
1. In the Inxpect Safety application click Configuration.
2. Optional. Add the desired number of sensors in the plane.
3. Define the position and inclination of each sensor.
4. Choose the area shape (only for 5.x sensors).
5. Define the safety working mode, detection distance, angular coverage, and restart timeout for each detection
field of each sensor.
6. Optional. Enable the Static object detection option for each detection field only if needed. For details, see
"Restart prevention function: static object detection option" on page44.
8.4.4 Configure the inputs and outputs
1. In the Inxpect Safety application, click Settings.
2. Click Digital Input-Output and define the input and output functions.
3. If the muting is managed, click Settings > Muting and assign the sensors to the groups according to the logic
of the digital inputs.
4. Settings > Restart function and choose the type of managed restart.
5. Click APPLY CHANGES to save the configuration.
8.4.5 Save and print the configuration
1. In the application, click APPLY CHANGES: the sensors will save the inclination set and the surrounding
environment. The application will transfer the configuration to the control unit, and once transfer is complete
it will generate a configuration report.
2. Click to save and print the report.
Note: to save the PDF, a printer must be installed on the computer.
3. Ask the authorized person for a signature.
8.4.6 Assign the Node IDs
Type of assignment
Note: if the connected sensors do not already have a Node ID assigned (e.g., at first startup), the system
automatically assigns them a Node ID during the installation procedure.