9. Troubleshooting
Example:
20 2020/11/18 16:47:25 [INFO] SENSOR #1 Detection access (field #1, 1200 mm/30°)
9.3.7 Detection exit
After at least one detection access event, a detection exit event related to the same field is logged when the
detection signal returns to its default no-motion status.
Depending on the selected verbosity level additional parameters are logged: the detection field number, the
sensor which detected the motion.
Format: Detection exit (field #n)
Example:
20 2020/11/18 16:47:25 [INFO] CONTROLUNIT Detection exit (field #1)
9.3.8 Dynamic configuration in use
At every change of the dynamic configuration, the new ID of the dynamic configuration selected is logged.
Format: Dynamic configuration #1
Example:
20 2020/11/18 16:47:25 [INFO] CONTROLUNIT Dynamic configuration #1
9.3.9 Muting status
Every change of the muting status of each sensor is logged as disabled or enabled.
Note: the event indicates a change of the muting status of the system. It does not correspond to the muting
request.
Format: Muting disabled/enabled
Example:
20 2020/11/18 16:47:25 [INFO] SENSOR#1 Muting enabled
9.3.10 Fieldbus connection
The Fieldbus communication status is logged as CONNECTED, DISCONNECTED or FAULT.
Format: Fieldbus connection CONNECTED/DISCONNECTED/FAULT
Example:
20 2020/11/18 16:47:25 [INFO] CONTROLUNIT Fieldbus connection CONNECTED
9.3.11 MODBUS connection
The MODBUS communication status is logged as CONNECTED or DISCONNECTED.
Format: MODBUS connection CONNECTED/DISCONNECTED
Example:
20 2020/11/18 16:47:25 [INFO] CONTROLUNIT MODBUS connection CONNECTED
9.3.12 Session authentication
The status of the session authentication and the interface used (USB/ETH) are logged.
Format: Session OPEN/CLOSE/WRONG PASSWORD/UNSET PASSWORD/TIMEOUT/CHANGE PASSWORD via
USB/ETH