EasyManuals Logo

Janus Mv Series User Manual

Default Icon
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
Page: 45
MV & LV SERIES ENGINEERED DRY CHEMICAL FIRE EXTINGUISHING SYSTEM
OPERATION, DESIGN, & SERVICE MANUAL
REV C
Document # DOC324
Issued: April 26, 2018
Revised: March 22, 2022
UL FILE # EX27541
HEIGHT
WIDTH
LENGTH
LOCATE NOZZLE AT MIDPOINT
OF ADJACENT MODULE EDGE
6 in (152 mm) MAXIMUM
FROM ENTRY POINT
8 ft (2438 mm)
MAXIMUM
TO LATERAL
MODULE
EDGE
TFP NOZZLE AS VIEWED DIRECTLY FROM BELOW:
Figure 3.2.4.2a Nozzle Placement for Total Flood Perimeter
Figure 3.2.4.2b Total Flood Perimeter Nozzle Top View
Table 3.2.4.2.1 TFP Nozzle Coverages
Maximum Module Volume 2,720 ft³ (77.02 m³) per Nozzle
Maximum Module Area
217.6 ft² (20.21 m²) per nozzle at 12.5 ft
(3810 mm) nozzle height
Maximum Module Height 12.5 ft (3810 mm)
Maximum Module Side Length 16 ft (4877 mm) either dimension
3.2.4.2 Total Flood - Module Perimeter Coverage
3.2.4.2.1 Nozzle Orientation
e Total Flood Perimeter (TFP) Nozzle,
(P/N 17809) is used to provide application of
extinguishing agent from the upper perimeter of
the module being protected. e nozzle is to be
installed through the top of the module, at the
closest point to the intersection of the module
wall and module top. e nozzle location,
laterally, is to be at the midpoint of the adjacent
module edge. [e nozzle may be offset laterally
(side to side) from the midpoint as long as the
maximum lateral horizontal distance from the
nozzle to the module edge does not exceed 8 ft
(2438 mm)] e tip of the nozzle must be within
6 in (152 mm) of its entry point. e nozzle
is to be installed vertically, with the orifices
pointing downward, and the engraved arrow
pointing into the protected module. e arrow
must be aligned perpendicular to the adjacent
wall, when viewed directly from below. Refer to
Figure 3.2.4.2a and 3.2.4.2b for proper nozzle
placement. e nozzle coverages are shown in
Table 3.2.4.2.1.
NOTE: e Janus Fire Systems® Engineered
Dry Chemical System has not been evaluated
by Underwriters Laboratories, Inc. with
respect to the total flood protection of hazards
incorporating unclosable openings exceeding
5% of the total hazard surface area.
Section 3 System Design

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Janus Mv Series and is the answer not in the manual?

Janus Mv Series Specifications

General IconGeneral
BrandJanus
ModelMv Series
CategoryFire Extinguisher
LanguageEnglish