Chapter 4 E1 Testing
Specifying test application settings
SmartClass E1 Tester User’s Guide 35
4 Do one of the following:
If you selected User Bit Pattern, in the BERT Pattern Settings menu,
select User Bit Pattern, and then specify the bit pattern you want to
use.
If you selected User Byte Pattern, in the BERT Pattern Settings menu,
select User Byte Pattern, and then specify the byte pattern you want
to use.
5 If you need to specify other settings for the test, press Cancel to return to
the Configuration menu.
The BERT pattern is specified.
Specifying Error/Alarm
settings
You can specify the error or alarm to be inserted into the traffic you are trans-
mitting.This is only available in the E1 BERT application.
To specify defects or anomalies
1 If you haven’t already done so, launch the E1 BERT application (see
“Launching an E1 test application” on page 28).
2 On the Error/Alarm menu, select Error/Alarm Settings, and then do one
of the following:
To specify defects or alarms, select Defects/Alarms, and then proceed
to step 3.
To specify anomalies or errors, select Anomalies/Errors, and then
proceed to step 4.
3 On the Defects/Alarms menu, select one of the following defects or
alarms:
Proceed to step 5.
Defect/Alarm Description
LOS Loss of signal
LOF Loss of framing
AIS Alarm indication signal
RDI Remote defect indication
MF AIS Multi frame AIS
MF RDI Multi frame RDI