FMS-2000C
LIT-12013508
46
Object instance Internal oat values Read or write
ADF-15 PID control loop 4 setpoint Read or write
ADF-16 Air change rate based on flow input at AI-1 Read only
ADF-17 Air change rate based on flow input at AI-2 Read only
ADF-18 Air change rate based on flow input at AI-3 Read only
ADF-19 Air change rate based on flow input at AI-4 Read only
ADF-20 Alarm relay 3 high setpoint Read or write
ADF-21 Alarm relay 3 low setpoint Read or write
ADF-22 Alarm relay 4 high setpoint Read or write
ADF-23 Alarm relay 4 low setpoint Read or write
ADF-24 AI-2 low alarm setpoint Read or write
ADF-25 AI-2 low warning setpoint Read or write
ADF-26 AI-2 high warning setpoint Read or write
ADF-27 AI-2 high alarm setpoint Read or write
ADF-28 AI-3 low alarm setpoint Read or write
ADF-29 AI-3 low warning setpoint Read or write
ADF-30 AI-3 high warning setpoint Read or write
ADF-31 AI-3 high alarm setpoint Read or write
ADF-32 AI-4 low alarm setpoint Read or write
ADF-33 AI-4 low warning setpoint Read or write
ADF-34 AI-4 high warning setpoint Read or write
ADF-35 AI-4 high alarm setpoint Read or write
ADF-36 TI-1 low alarm setpoint Read or write
ADF-37 TI-2 low warning setpoint Read or write
ADF-38 TI-1 high warning setpoint Read or write
ADF-39 TI-1 high alarm setpoint Read or write
ADF-40 TI-2 high alarm setpoint Read or write
ADF-41 TI-2 low warning setpoint Read or write
ADF-42 TI-2 high warning setpoint Read or write
ADF-43 TI-2 high alarm setpoint Read or write
ADF-44 Humidity network variable, writable Read or write
ADF-45 Temperature network variable, writable Read or write
ADF-46 Air changes network variable, writable Read or write
ADF-47 Differential pressure network variable, writable Read or write
ADF-48 Air flow based on flow input at AI-1 Read only
ADF-49 Air flow based on flow input at AI-2 Read only
ADF-50 Air flow based on flow input at AI-3, default: supply flow Read only
ADF-51 Air flow based on flow input at AI-4, default: exhaust flow Read only
ADF-52 Volumetric offset, supply flow - exhaust flow Read only
ADF-53 Volumetric offset setpoint Read or write
ADF-54 AO-1 override level Read or write
ADF-55 AO-2 override level Read or write
ADF-56 AO-3 override level Read or write
ADF-57 AO-4 override level Read or write
ADF-58 AI-1 deadband setting Read or write

Other manuals for Johnson Controls FMS-2000C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls FMS-2000C and is the answer not in the manual?

Johnson Controls FMS-2000C Specifications

General IconGeneral
BrandJohnson Controls
ModelFMS-2000C
CategoryController
LanguageEnglish

Related product manuals