IFC-3030 Installation Manual — P/N 52024:C 08/05/2005 11
Section 2: System Overview
2.1 System Description
2.1.1 Standard Features
2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
• Rubberized keypad with a standard “QWERTY” keyboard layout, a 640-character LCD
display, indicator LEDs, and switches.
• Separately ordered Loop Control Modules and Loop Expander Modules provide up to ten
SLC loops.
• Optional equipment includes: ACS devices, UDACT Universal Digital Alarm Communicator/
Transmitter, ACM-8R remote relay module to provide additional relay points, audio and voice
components, and panel circuit modules.
2.1.3 System Limitations
System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries).
• Connections to easily mount from one to
ten Signaling Line Circuit (SLC) loops
• Network operation
• Uses VIEW® early warning fire detection
and the FlashScan® or CLIP families of
detectors and modules
• Alarm, Trouble, Supervisory and Security
relays
• Support for 32 annunciator addresses with
either 64 or 96 points each (depending on
the capability of the annunciator)
• Supports Style 4, Style 6, Style 7 SLC
loops
• Logic Equations
• Multi-line display
• Ability to activate local sounder or relay
bases in alarm or pre-alarm
• Alarm verification pre-alarm indication
(NYC)
• Supervisory duct detectors
• Supports AWACS algorithms
• EIA-485 connections for wiring ACS
annunciators (including LDM custom
graphic annunciators), TM-4 transmitter
• EIA-232 connection for printer
• Autoprogram feature for faster
programming of new devices
• Easy connection to VeriFire™ Tools
programming utility
• The basic system power supply is
addressable, charges sealed lead-acid
batteries ranging in capacity from 25 to 200
amp hours, and provides 4.5 amps of power
for use by the CPU.
• Easy connection to auxiliary power
supplies and battery chargers for custom
design of very large systems.
• Diagnostic LEDs and switches
• Ground fault detection
• Supports up to 12 panel circuit modules,
including input module IZM-8RK
• Support for Remote Text Display
(LCD-160)
• Support for Display and Control Center
(DCC) functionality