IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 101
Abort Switches Releasing Applications
How to Program a Manual Release Switch
The following contains information needed to program a Manual Release switch for a monitor
module
.
Description A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-
12LRA)—used to monitor a pull station for the manual release of agents. A Manual Release
switch overrides all timers, such as Delay Time or a Soak Time. Multiple monitor modules
can be programmed with a
MAN. RELEASE type code. They work like multiple conventional
manual release switches on a conventional zone.
Program Select a monitor module for the manual release function. While programming this module
(refer to “Module Point” on page 43 for instructions),
1. Select the
MAN. RELEASE type code.
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example
A programming example of a monitor module programmed as an manual release switch for releasing zone
ZR05.
Figure B.10 Monitor Module Configured as a Manual Release Switch
SYSTEM
NORMAL
SYSTEM
ACTIVATED
Detector
ZR05
NBG-12LRA station with Manual Release Lever
Monitor
Module
Type Code
MAN. RELEASE
SLC
output
module
SLC
output
module