IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 61
Autoprogram Menu Program
Add New Points
When the REVIEW soft key is pressed, the panel will individually display each new SLC or panel
circuit point found during autoprogramming. The screen below uses an SLC detector point as an
example. A new panel circuit point will display “NEW PANEL MODULE FOUND AT PXX”
instead of the message below.
Figure 3.51 Autoprogram Confirmation Screen (New SLC Point)
Soft Keys
YES: Press this soft key to install the new point into the panel’s database.
EDIT: Press this soft key to advance to the point programming menu for the new point. (This
option is available for SLC points only, not for panel points. The
EDIT soft key will not appear for
panel modules).
NO: Press if the point will not be installed.
Error and Discrepancy Resolution
Pressing the REVIEW soft key will bring up screens that provide the means to resolve any errors or
discrepancies found during autoprogram.
Figure 3.52 Autoprogram Confirmation Screen (Missing Point)
AUTOPROGRAM CONFIRMATION
NEW DEVICE FOUND AT LXXXDXXX
ADD POINT?
YES NO
EDIT BACK
AUTOPROGRAM CONFIRMATION
NO DEVICE FOUND AT LXXDXXX
DELETE POINT?
YES NO
BACK