36 Installation—Installing the FC-2000
2. Use only the compatible, UL Listed 2-wire smoke detectors that are
listed in the Device Compatibility document in the Fire Management
Accessories Manual (FAN 445).
3. For connection of 4-wire smoke detectors and initiating devices
requiring separate 24 VDC power, refer to the Applications section of
this document.
4. Wire initiating devices according to the manufacturer’s instructions
packaged with each device.
5. For Canada, model N-ELR End-of-Line Resistor Assembly required.
6. Maximum line resistance due to wiring is 100 ohms.