Art. No. SC 1000 KNX
the KNX bus. There is also the option
not to implement any function when a
button is pressed.
The following parameters are only visible for the function "Dimming (start/stop)"...
Time between switching
and dimming
(100ms...50000ms)
100...400...50000 This parameter defines the duration of a
sensor surface operation for triggering a
dimming telegram. A sensor operation
shorter than the time set here triggers
switching telegrams. Dimming telegrams
are transmitted to the bus by sensor
operations that are longer than the time
set here. A stop telegram is triggered
automatically by releasing a long
pressed sensor element whereby a
dimming process is stopped at the
current brightness value.
Displaying icons Yes
No
An icon can be displayed in the lower
area of the channel display element
(setting: Yes). The "Lighting" icon is then
always used. The character of the status
icon changes depending on the dimming
state thereby enabling the brightness
state of the activated KNX channel to be
read clearly.
The icon can be omitted optionally in the
display (setting: no).
Displaying status value Yes
No
A status value can be displayed
optionally below the text name, which
displays brightness values in plain text
("0...100 %") depending on the object
value of the dimming value feedback of
the dimmer actuator addressed. This
parameter defines the visibility of the
status value in the display element of
the channel.
After a device reset, the display shows
"---%" until a feedback object value of
the status text is received.
Surface evaluation Button function (single
surface)
Rocker function (double
surface)
The operating element of the channel
can be evaluated optionally on the touch
surface as a rocker switch (double-
surface principle) or as a button (single
surface principle). This parameter
defines the sensor evaluation and thus
specifies the character of the sensor
element in the display.
With the function as a button, the
operating element can be touched
anywhere. The preset push-button
function will then always be executed.
With the rocker function, the operating
element is divided into two sensor
areas. These sensor areas are one
above the other and must be operated
separate from each other. It is not
permissible to operate both sensor
Page 256 of 347
Software "Smart Control 501511"
Parameters