Art. No. SC 1000 KNX
areas of a rocker simultaneously.
The following parameters are only visible for the function "Dimming (Brightness value)"...
Time between switching
and dimming
(100ms...50000ms)
100...400...50000 The sensor element of the function
"dimming (brightness value)" is always
executed as a rocker function and
distinguishes between short and long
operations. A short sensor operation
triggers value telegrams "100 %" or
"0 %", depending on the operated
sensor surface + or -. In this way, as
with a switching operation, the activated
load is switched on and off. Brightness
value telegrams are transmitted to the
bus gradually in a defined time interval
by means of long operations of the
sensor surfaces + or -. The device then
increases or decreases the value
cyclically during the operation
depending on the value transmitter level
configured in the ETS and transmits the
values as a brightness setting. The
value sequence generated in this way is
converted to a dimming process by the
activated dimmer actuator.
The time for executing a switching
operation (0% or 100% / shorter
operation than the time set here) or
value adjustment (longer operation than
the time set here) can be configured
here.
Displaying icons Yes
No
An icon can be displayed in the lower
area of the channel display element
(setting: Yes). The "Lighting" icon is then
always used. The character of the status
icon changes depending on the dimming
state thereby enabling the brightness
state of the activated KNX channel to be
read clearly.
The icon can be omitted optionally in the
display (setting: no).
Displaying status value Yes
No
A status value can be displayed
optionally below the text name, which
displays brightness values in plain text
("0...100 %") depending on the object
value of the dimming value feedback of
the dimmer actuator addressed. This
parameter defines the visibility of the
status value in the display element of
the channel.
After a device reset, the display shows
"---%" until a feedback object value of
the status text is received.
Page 257 of 347
Software "Smart Control 501511"
Parameters