Art. No. SC 1000 KNX
Function: Channel function "ASCII Text"
Object
h
138
Function
ASCII text 2
Name
D.Input
Channel 1
1
Type
14
byte
DPT
16.000
Flag
C, W, T,
(R)
2
Description 14-byte object, which can receive ASCII character chains of maximum 14
characters to show a running text on the display (Part 2 of the running text).
Objects for weather stations display page (alternative to KNX channels 24...30)
Function: Weather station display
Object
h
227
Function
Visual. Wind speed
Name
W.Wind speed
Type
2 byte
DPT
9.005
Flag
C, W, -, (R)
3
Description 2-byte object to receive a value telegram for the determined wind speed of a
KNX weather station. The measured value must be made available to the
device via the bus in "m/s" in compliance with KNX DPT 9.005. According to
the parameter setting of the measured value, a conversion and display in the
formats "m/s", "km/h" or "Bft (Beaufort)" takes place if necessary.
Function: Weather station display
Object
h
228
Function
Visualization of precipitation
Name
W.Precipitation
Type
1-bit
DPT
1.xxx
Flag
C, W, -, (R)
3
Description 1 bit object to receive a switching telegram with which the precipitation
situation ("0" = no rain / "1" = rain) can be visualized.
Function: Weather station display
Object
h
229
Function
Visual. Brightness sensor 1
Name
W.Brightness
sensor 1
Type
2 byte
DPT
9.004
Flag
C, W, -, (R)
3
Description 2-byte object to receive a value telegram for any brightness value (e.g. "Sun
East" of a KNX weather station). The measured value must be made available
to the device via the bus in the format "lux" in compliance with KNX DPT
9.004. The brightness measured value must be transmitted to the device via
the bus in the format "lux" in compliance with KNX DPT 9.004. The measured
value is converted by the device so that it is displayed in "kLux".
1: The objects have been described for channel 1 as an example. The objects for the other
channels are defined in the same way by shifting the object number and changing the object
name.
2: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
3: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.