DIP Switch Factory Settings - 2-pipe System
DIP Switch Factory Settings - 4-pipe System
When using control configuration C2, all slave units must be fitted
with a clip-on temperature sensor.
KaControl für Venkon
INSTALLATIONS- UND BEDIENUNGSANLEITUNG
1.48
Venkon
35
DIP
2-pipe
Functions
C1 C2
DIP1 OFF OFF Clip-on temperature sensor not fitted
DIP2 ON ON H/C changeover via digital input DI2
DIP3 OFF OFF Operating function lock disabled
DIP4 OFF OFF 2-pipe system
DIP5 OFF OFF OFF must be set
DIP6 ON OFF
OFF=Room control to clip-on temperature sensor
ON=Room control to sensor in the KaController
DIP
4-pipe
Functions
C1 C2
DIP1 OFF OFF Clip-on temperature sensor not fitted
DIP2 OFF OFF Digital input DI2 not operational
DIP3 OFF OFF Operating function lock disabled
DIP4 ON ON 4-pipe system
DIP5 OFF OFF OFF must be set
DIP6 ON OFF
OFF=Room control to clip-on temperature sensor
ON=Room control to sensor in the KaController
DIP switch 2-pipe system control
configuration C1
DIP switch 2-pipe system control
configuration C2
DIP switch 4-pipe system control
configuration C2
DIP switch 4-pipe system control
configuration C1