Special requirements for open and half-open cooling systems:
Impurities Mechanical impurities in half-open cooling systems can be counteracted when
appropriate water 󰘰lters are used.
Salt concentration The salt content can increase through evaporation at half-open systems. Thus
the water is more corrosive. Adding of fresh water and removing of process water
works against.
Algae and myxobacteria Algae and myxobacteria can arise caused by increased water temperature and
contact with atmospheric oxygen. The algae and myxobacteria clog the 󰘰lters and
obstruct the water-󰘱ow. Biocide containing additives can avoid this. Especially at
longer o󰘯 periods of the cooling circuit preventive maintenance is necessary.
Organic materials The contamination with organic materials must be kept as small as possible, be-
cause separate slime can be caused by this.
NOTICE
Loss of the warranty claims
Damages at the unit which are caused by clogged, corroded heat sinks
or other obvious operating errors, leads to the loss of the warranty claims.
6.1.4 Connection to the cooling system
Screw in connecting duct in accordance with the manual.
The connection to the coolant must be carried out with 󰘱exible, pressure-resistant
hoses and secured with clamps.
Pay attention to 󰘱ux direction and check tightness !
The cooling 󰘱ow must always be started before starting the KEB COMBIVERT.
The connection to the cooling system can occur as closed or open cooling circuit. The
connection to a closed cycle cooling circuit is recommended, because the danger of
contamination of coolant is very small. Preferably also a monitoring of the pH value of
the coolant should be installed.
Pay attention to a corresponding cable cross section at required equipotential bonding
in order to avoid electro-chemical procedures.
6.1.5 Coolant temperature and moisture condensation
Theinlettemperaturemaynotexceed40°C.Themaximumheatsinktemperature
is60°Cor80°Cdependingonthepowerunitandoverloadcapacity(see„Technical
data“).Toensureasafeoperationthecoolantoutputtemperaturemustbe10Kbelow
this temperature.
Due to high air humidity and high temperatures it can lead to moisture condensation.
Moisture condensation is dangerous for the drive converter, because the drive converter
can be destroyed through eventual occuring short-circuits.
NOTICE
The user must guarantee that any moisture condensation is avoided !