Hardware installation
23 / 156
STANDARD MODE + ADDRESSING
DSW2.6=ON
The charging procedure in STANDARD mode is
carried out automatically by the charging station
without higher-ranking control system.
The charging station has the static IP address:
[192.168.25.xx]
Set the desired IP address with the DIP-switches
DSW2.1 to DSW2.4 (see “Addressing”).
Example: address 17
LOAD MANAGEMENT MODE + ADDRESSING
DSW2.6=OFF
The charging procedure in LOAD
MANAGEMENT mode is controlled by a higher-
ranking load management system.
Since multiple charging stations are located in a
network; an addressing of the charging stations is
necessary.
Set the desired IP address with the DIP-switches
DSW2.1 to DSW2.4 (see “Addressing”).
Example: address 17
ADDRESSING (for all modes without DHCP)
DSW2.1 to DSW2.4
If multiple charging stations are located in a net-
work, an addressing of the charging stations is
necessary.
The addressing is done via the DIP-switches
DSW2.1 to DSW2.4. The settable Ethernet ad-
dresses start at 10 + DIP-switch setting.
With the 4-bit addressing, the addresses 11 to 26
are usable [192.168.25.xx].
DSW2.1 = Address Bit 2
0
(Value=1)
DSW2.2 = Address Bit 2
1
(Value=2)
DSW2.3 = Address Bit 2
2
(Value=4)
DSW2.4 = Address Bit 2
3
(Value=8)
Example for address "17":
DSW2.1 = ON (value=1)
DSW2.2 = ON (value=2)
DSW2.3 = ON (value=4)
DSW2.4 = OFF (value=0)
Address= 10 + 1 + 2 + 4 + 0 = 17
COMMISSIONING MODE (DSW2.8)
Function
DIP-switch
Figure
Commissioning mode
activate
D2.8
ON=yes