EasyManuals Logo

KMC Controls SimplyVAV BAC-8001 User Manual

KMC Controls SimplyVAV BAC-8001
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Procedure Steps Sensor display
3.
When the
Set
Point
button is pressed for the last digit, the
new password is saved and the display advances.
4 Change Password 2.
Note: Entering four zeros (0000) removes the password.
1.
Press the or buttons to change the first digit.
2.
Press the
Set
Point
button to select the next digit. Repeat
for all four digits.
3.
When the
Set
Point
button is pressed for the last digit, the
new password is saved and the display advances.
PSW2
OOOO
5 Set the local unoccupied
override timer.
Applies only to STE-6017
sensors.
1.
Press the or buttons to set the local
unoccupied override timer. The value will change in 1
minute increments.
2.
Press the
Set
Point
button to save the setpoint and advance
to the next function.
3O
OVRD
6 Set the standby time
Applies only to STE-8201
digital sensors.
1.
Press the or buttons to set the time for the
standby time. The value will change in 1 minute
increments.
2.
Press the
Set
Point
button to save the setpoint and advance
to the next function.
15
7 Set discharge air temperature
limiting.
Not used for all models.
Required for reheat.
1.
Press the or buttons to enable or disable
discharge air temperature limiting.
2.
Press the
Set
Point
button to save the setpoint and advance
to the next function.
DISABLE
DAT
8 Set the automatic occupancy
mode.
Requires a discharge air
temperature sensor.
1.
Press the or buttons to enable or disable
automatic occupancy.
2.
Press the
Set
Point
button to save the setpoint and advance
to the next function.
Enable The controller will automatically changed
to the unoccupied state when it detects the loss
of primary air supply.
Disable The controller will remain in the occupied
mode regardless of the primary air supply.
DISABLE
AUMD
Procedure to set the advanced options (continued)
Section 4: Configuring the controllers KMC Controls, Inc.
34 Revision H

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KMC Controls SimplyVAV BAC-8001 and is the answer not in the manual?

KMC Controls SimplyVAV BAC-8001 Specifications

General IconGeneral
BrandKMC Controls
ModelSimplyVAV BAC-8001
CategoryController
LanguageEnglish

Related product manuals