Procedure Detailed steps Sensor display
1.
Press the or buttons to set the minimum
cooling setpoint. The setpoint will change in 0.5°
increments.
2.
Press the
button to save the setpoint and advance
to the next function.
4 Set the maximum heating
setpoint.
This setpoint limits the highest temperature a user can
enter as the active setpoint.
1.
Press the or buttons to set the maximum
heating setpoint. The setpoint will change in 0.5°
increments.
2.
Press the
button to save the setpoint and advance
to the next function.
5 Set the occupied cooling
setpoint.
This setpoint is used as the active setpoint when the
space is occupied.
1.
Press the or buttons to set the occupied
cooling setpoint. The setpoint will change in 0.5°
increments.
2.
Press the
button to save the setpoint and advance
to the next function.
Note: This setpoint can also be changed as
described in the topic Changing the room
setpoint on page 19.
6 Set the occupied heating
setpoint.
This setpoint is used as the active setpoint when the
space is occupied.
1.
Press the or buttons to set the occupied
heating setpoint. The setpoint will change in 0.5°
increments.
2.
Press the
button to save the setpoint and advance
to the next function.
Note: This setpoint can also be changed as
described in the section Changing the room
setpoint on page 19.
Procedure to set the temperature setpoints (continued)
Section 4: Configuring the controllers KMC Controls, Inc.
24 Revision H