Controllers with a connected motion sensor change to Occupied upon the detection of
primary airflow and motion in the space. The unit will remain in the OCCUPIED state as long
as periodic motion is detected and primary airflow continues. If motion stops, the controller
changes to STANDBY.
Unoccupied
The controller Occupancy mode changes to UNOCCUPIED when it detects a loss of
primary airflow. While in the UNOCCUPIED state, the controller will fully open the damper in
an attempt to reach the maximum airflow setpoint.
Loss of primary airflow is defined as less than 25% of the requested flow for at least 5
minutes. The Occupancy mode changes to Occupied or Standby once the actual airflow
is at least 30% of the requested flow.
Standby
In units with a connected motion sensor, the controller starts in STANDBY and changes to
OCCUPIED after detecting motion in the space. Motion in the space is defined as two
movements detected within 5 minutes. The controller will change back to STANDBY after a
lack a lack of motion for the period specified by the variable Standby Time.
Standby mode is not valid for controllers without a motion sensor, unless commanded by a
building management system.
Space setpoints
There are four temperature setpoints each for heating and cooling for a total of eight
setpoints.
l Active cooling
l Occupied cooling
l Unoccupied cooling
l Standby cooling
l Active heating
l Occupied heating
l Unoccupied heating
l Standby heating
Types of setpoints
The SimplyVAV controllers may use any of the following setpoints based on a user entered
setpoint or the state of occupancy and standby which is described in the topic Occupancy
sequence on page 50.
SimplyVAV Section 7: Sequences of operation
Revision H 51

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KMC Controls SimplyVAV BAC-8001 and is the answer not in the manual?

KMC Controls SimplyVAV BAC-8001 Specifications

General IconGeneral
BrandKMC Controls
ModelSimplyVAV BAC-8001
CategoryController
LanguageEnglish

Related product manuals