54 / 65 Issued: 29.11.2012 Version: KR C4 Interbus 1.1 V2 en (PDF)
Interbus 1.1
%1 Error on starting
slave ring without
master ring.
An error occurred in a
firmware service
when starting the
slave ring without
starting the master.
The cause depends
on the return values
of the firmware ser-
vices.
The slave ring is not
activated and no I/O
data are exchanged.
Depends on the
return value of the
firmware services.
%1 Negative return
value received from
one command in the
SVC file.
A negative return
value was received
from the firmware
when executing a
command from the
SVC file.
The message has no
effect on the execu-
tion of the SVC file.
Other errors will
occur, depending on
which firmware ser-
vice has failed.
Activate logging of the
Interbus driver with
level debug and
check the return value
of the firmware ser-
vice. The physical bus
configuration does not
match that config-
ured in the SVC file.
Message Reason Effect Remedy