Basic units in the power range 0.25 ... 2.2 kW
Terminal assignment - Standard I/O E82ZAFSC
7
Extensions for automation
7.2
7.2.2
L
7.2-6
EDS82EV903-1.0-11/2002
X3/
13
Signal type Function Level
Lenze setting: Bold print
62 Analog
output
Output frequency 0 ... + 6 V
0 ... + 10 V
1)
7 - GND1, reference potential for analog signa ls -
8 Analog input
Act. or setpoint input
Change range using the DIP switch and C0034
• Master voltage 0 ... +5 V
0 ... +10 V
-10V...+10V
2)
• Master current 0 ... +20 mA
+4 ... +20 mA
+4 ... +20 mA (open-circuit
monitored)
9 - Internal, stabilised DC voltage supply for setpoint
potentiometer
+5.2 V
20 - Internal DC voltage supply for control of digital inputs
and output
+20 V ± 10 % (ref.: X3/7)
28 Controller inhibit (CINH) 1 = START
E1
3)
Activation of JOG frequencies
E1 E2
JOG1 = 20 Hz
JOG1 1 0
E2
3)
JOG2 = 30 Hz
JOG2 0 1
Di
ital in
uts
JOG3 = 40 Hz
JOG3 1 1
E3
DC-injection brake (DCB) 1=DCB
E4 Change of direction of rotation
E4
CW/CCW rotation
CW 0
CCW 1
39 - GND2, reference potential for digital s ignals -
A1
Digital output
Ready for operation with
– internal supply:
– external supply:
0 ... +20 V
0 ... +24 V
59 - DC supply for X3/A1
– internal (bridge to X3/20):
–external:
+20 V
+24 V
1)
Output level 0 ... + 10 V: Adapt offset (C0109/C0422) and gain (C0108/C0420)
2)
Adjust o f f set (C0026) and gain (C0027) separately for each function module:
After replacing the function module or the basic device
After loading the Lenze setting
3)
Optional frequency input 0 ... 10 kHz single-tracked or 0 ...1 kHz double-tra cke d, configuration via C0425
Terminal assignment