Basic units in the power range 75 ... 90 kW
Power connections
6
Basic unit wiring
6.8
6.8.2
L
6.8-4
EDS82EV903-1.0-11/2002
6.8.2 Power connections
Mains connection 400/500 V
0
L1
L2
L3
N
PE
+UG
-UG
Z1
PE
L1
L2
L3
3/PE AC 400V
T2
T1
L2
L3
L1
3
3
4
L1
L2
L3
+UG
PE
l
3/PE AC 400V
-UG
L1, L2, L3
+UG, -UG
PE
30 Nm
264 lb-in
M10
PE
L1
L2
L3
+UG
PE
l
L1’ L2’ L3’
Gerät / Load
L1 L2 L3 PE
Netz / Line
3/PE AC 400V
Z1
-UG
L1, L2, L3
+UG, -UG
PE
30 Nm
264 lb-in
M10
PE
3
2
T1
T2
2,5 Nm
22,1 lb-in
L1
L2
L3
+UG
PE
l
-UG
L1 L2 L3
3/PE AC 400V
PE
+UG, -UG
PE
M10
30 Nm
264 lb-in
E82EV753K4:
6-12 Nm (53,1-106,2 lb-in)
E82EV903K4:
10-20 Nm (88,5-177 lb-in)
L1, L2,
L3
3
4
1
ϑ>
8200vec290
Fig. 6.8-2 Mains connection 75 ... 90 kW
0
Connection with mains choke
1
Connection with footprint mains filter
2
Connection with built-on mains filter
3
Connection brake chopper ( ^ Operating Instructions for the brake chopper )
4
Connection of temperature monitoring for mains filter (thermal contact)
Z1 Mains choke/mains filter
Fuses and cable cross-sections
8200 vector mains In s t allation to EN 60204-1 Installation to UL
1)
FI
2)
Fuse L1, L2, L3, PE [mm
2
] Fuse L1, L2, L3, PE [AWG]
E82EV753K4B
3/PE AC 320 V - 0 % ... 550 V +0 %
M160 A 70 175 A 2/0
E82EV903K4B
5
z-
...
5
z+
DC 450 V -0 % ... 775 V +0 %
M200 A 95 200 A 3/0
≥
m
1)
Use UL-approved cables, fuses and fuse holders only. UL fuse: 500 ... 600 V, tripping characteristic ”H” or ”K5”
2)
All-current sensitive e.l.c.b.
Observe national and re gional regulations (e. g. VDE 0113, EN 60204)