Basic units in the power range 0.25 ... 2.2 kW
Power connections for 230 V mains voltage
6
Basic unit wiring
6.4
6.4.2
L
6.4-4
EDS82EV903-1.0-11/2002
6.4.2 Power connections for 230 V mains voltage
(
((
( Stop!
l Controller type E82EVxxxK 2 C must only be connected to a
mains voltage of 1/N/PE AC 180 ... 264 V or 3/PE AC 100 ...
264 V. Higher mains voltages will destroy the controller!
l The discharge current to PE is > 3.5 mA. EN 50178 requires a
fixed installation. Double PE connection required.
E82EV551K2B
E82EV751K2B
X1.1
X1.1
E82EV251K2B
E82EV371K2B
E82EV152K2B
E82EV222K2B
X1.1
N
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
PE
L1
1/N/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1 PE
L2 PEL1
2/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1 PE
PE
L1 L2 L3
3/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1 PE
PE
L1 L2
2/PE AC 230 V/240 V
+UG -UG
L1
L3
PE
L2/N
PE
L1 N
1/N/PE AC 230 V/240 V
+UG -UG
L1
L2/N
L3
PE
PE
L1 N
1/N/PE AC 230 V/240 V
L1
L2/N
PE
L2/N
PE
L1 L2 L3
3/PE AC 230 V/240 V
+UG -UG
L1
L3
PE
2/PE AC 230 V/240 V
PE
L1
L1
L2/N
PE
L2
00
8200vec012
Fig. 6.4-2 Mains connection 230/240 V 0.25 ... 2.2 kW
0
Use two separate cables 1.5 mm
2
to connect the terminals!
X1.1/+UG,
X1.1/-UG
DC supply (DC-bus operation - see Operating Instructions)
E82EV222K 2C Operation only with mains choke
Mains connection 230/240 V
8200 vector 0.25 ... 2.2 kW
Show/Hide Bookmarks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze E82EV751K4C and is the answer not in the manual?

Lenze E82EV751K4C Specifications

General IconGeneral
BrandLenze
ModelE82EV751K4C
CategoryDC Drives
LanguageEnglish

Related product manuals