Code table
10
Function library
10.20
L
10.20-16
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0138* Process controller
setpoint 1
(PCTRL1-SET1)
0.00 -650.00 {0.02 Hz} 650.00 The value set will b e lost wh en
switching the mains!
• Selection if C0412/4 = FIXED-FREE
• Display if C0412/4 ≠ FIXED-FREE
^ 10.10-5
C0140* Additive frequency
setpoint
(NSET1-NADD)
0.00 -650.00 {0.02 Hz} 650.00 • Selection via function j of the
keypad or the parameter channel
• Is added to main setpoint
• Value is stored when switching the
mains or removing the keypad
^ 10.8-15
C0141* Setpoint
normalisation
0.00 -100.00 {0.01 %} 100.00 The value set will be lost wh en
switching the mains!
Only effective i f C0127 = 1
Reference: C0011
C0142
v
Start condition 1
0 Automatic restart after mains connection
inhibited
Flying restart not active
Start after HIGH-LOW-HIGH changes at
X3/28
^ 10.5-1
1 Automatic start, if X3/28 = HIGH
Flying restart circuit not active
2 Automatic restart after mains connection
inhibited
Flying-restart circuit active
Start after HIGH-LOW-HIGH changes at
X3/28
3 Automatic start, if X3/28 = HIGH
Flying restart circuit active
C0143* Selection of 0
0 Max. output frequency (C0011) ... 0 Hz
Motor speed selected for the indicated ^ 10.5-1
v
flying-restart
1 Last output frequency ... 0 Hz
range
2 Frequency setpoint addition (NSET1-NOUT)
The corresponding value is input after
3 Act. process controller value (C0412/5) a ddition
(PCTRL1-ACT)
controller enable.
C0144
v
No temperature
depending chopper
frequency derating
1 0 No temperature-depending chopper frequenc y
derating
When operating with a chopper frequency
of16kHzitisalsopossibletoderateitto4
kHz. The behaviour can be changed under
C0310.
^ 10.4-3
C0144
v
No temperature
depending chopper
frequency derating
1 Automatic chopper frequency derating to 4 kHz, if
ϑ
max reaches
-5°C
^ 10.4-3
C0145* Process controller 0
0 Total setpoint (PCTRL1-SET3) Main setpoint + additional setpoint
^ 10.10-5
v
setpoint source
1 C0181 (PCTRL1-SET2)
• Setpoint selection not possible via
–JOGvalues
– j function of the keypad
– C0044, C0046 and C0049
in connection with manual
remote
2 C0412/4 (PCTRL1-SET1)
changeover, skip frequencies, ramp
function generator, additional setpoint
• Activate the automatic DC-injection
brake (auto DCB) with C0019 = 0 or
C0106 = 0