Parameter Name / value range / [default seng] Info
0x400E:002
(P505.02)
NetWordIN1 funcon: Bit 1
(NetWordIN1 fct.: NetWordIN1.01)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 1 of the mappa-
ble NetWordIN1 data word.
0 Not acve
0x400E:003
(P505.03)
NetWordIN1 funcon: Bit 2
(NetWordIN1 fct.: NetWordIN1.02)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 2 of the mappa-
ble NetWordIN1 data word.
3 Acvate quick stop
0x400E:004
(P505.04)
NetWordIN1 funcon: Bit 3
(NetWordIN1 fct.: NetWordIN1.03)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 3 of the mappa-
ble NetWordIN1 data word.
0 Not acve
0x400E:005
(P505.05)
NetWordIN1 funcon: Bit 4
(NetWordIN1 fct.: NetWordIN1.04)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 4 of the mappa-
ble NetWordIN1 data word.
8 Run forward (CW)
0x400E:006
(P505.06)
NetWordIN1 funcon: Bit 5
(NetWordIN1 fct.: NetWordIN1.05)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 5 of the mappa-
ble NetWordIN1 data word.
18 Acvate preset (bit 0)
0x400E:007
(P505.07)
NetWordIN1 funcon: Bit 6
(NetWordIN1 fct.: NetWordIN1.06)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 6 of the mappa-
ble NetWordIN1 data word.
19 Acvate preset (bit 1)
0x400E:008
(P505.08)
NetWordIN1 funcon: Bit 7
(NetWordIN1 fct.: NetWordIN1.07)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 7 of the mappa-
ble NetWordIN1 data word.
4 Reset error
0x400E:009
(P505.09)
NetWordIN1 funcon: Bit 8
(NetWordIN1 fct.: NetWordIN1.08)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 8 of the mappa-
ble NetWordIN1 data word.
0 Not acve
0x400E:010
(P505.10)
NetWordIN1 funcon: Bit 9
(NetWordIN1 fct.: NetWordIN1.09)
•
Seng can only be changed if the inverter is inhibi-
ted.
•
For further possible sengs, see parameter
0x400E:001 (P505.01). ^ 175
Denion of the funcon that is to be triggered via bit 9 of the mappa-
ble NetWordIN1 data word.
5 Acvate DC braking
Conguring the network
General network sengs
179