6 EtherNet/IP
Cyclic Data Access (Implicit Messaging)
38 Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015
12. The corresponding tags will then be created in the controller tags of the project as shown herein.
To understand this from the above configuration we named the drive “My_i550_Drive”. There are three sets
of tags labeled “My_i550_Drive”:
[:C] for the Configuration assembly (1)
[:I] for the Input Assembly (101 in this example)
[:O] for the Output assembly (100 in this example)
13. Click on the [+] and expand the [My_i550_Drive:O] data to reveal all four words that make up the Output as-
sembly.
14. The example RSLogix™ 5000 project contains aliasing for all bits in the assemblies. The process below is the
basic workflow to create an alias tag in RSLogix™ 5000. To begin, select "Controller Tags" from the navigation
tree. Now right click next to any tag and select "New Tag…”