6 EtherNet/IP
Cyclic Data Access (Implicit Messaging)
Lenze · Inverter i550 - Cabinet · Ethernet Manual · 0.1 EN · 12/2015 39
15. Enter a meaningful name for the tag. Change the Type to "Alias". Then in the Alias For field browse to the de-
sired bit or word. In this example, Run Rev is the drive output assembly word 0 bit 1. Finally, select "Create"
to add the new alias tag to the database.
16. Implicit Messaging Timeout
Class 1 connections are monitored by watchdog timeout given in the forward open command while estab-
lishing a connection. It is often desirable to set a fault timeout condition to prevent the drive from operating
in a runaway condition or loss of communications. In case the class#1 connection expires, the defined reac-
tion in 0bject 0x2859 raised.