32
MultiSITE MS8000 Series Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
Conguration Parameters Default Value Signicance and Adjustments
Fan Menu (Fan Sequence)
Default Value = L-H-A
Fan Sequence configuration applies to “3 speed” and “ECM” fan type
The selected fan sequence in this menu dictates the Fan button options displayed on the
Home screen of the Room Controller.
L-M-H: 3-Speed configuration
L-H: 2-Speed configuration
L-M-H-A: 3-Speed configuration with Auto fan speed. Auto Mode operation is dependent on
Auto Fan parameter.
L-H-A: 2-Speed configuration with Auto fan speed mode. Auto Mode operation is dependent
on Auto Fan parameter.
On-Auto: Single Speed configuration. Auto selection will activate fan on demand. On selec-
tion will keep the fan On in occupied, standby and override mode, and will activate fan
based on demand in unoccupied mode.
Choices: On-Auto, L-M-H, L-H, L-M-H-A and L-H-A
Auto Fan Func. (Automatic Mode Fan
Function)
Default value: AS
Fan Sequence configuration applies to “three (3) speed” and “ECM” fan type
Auto Speed Fan Mode operation for Fan Menu (L-M-H-A) or (L-H-A).
AS: In Occupied, Standby and Override modes, the Fan stays ON at low speed even if
there is no demand for Heating or Cooling. In Unoccupied mode the Fan turns Off when
there is no demand for Heating or Cooling.
AS/AD: In any Occupancy mode, the Fan turns Off all speeds when there is no demand for
Heating or Cooling.
Choices: AS or AS/AD
MS8350 Configuration 3 / 9
CONFIGURATION SCREENS
MS8350 Conguration 3 / 9
Figure 26: MS8350 Conguration 3 / 9 Display.
Table 15: MS8350 Conguration 3 / 9 Parameter Details.
For MS8350 Only