100 
 
Closed). The input terminal does not have to be closed continuously to trigger Fast Stop. It will 
trigger Fast Stop even if the closure is momentary. Different from the normal deceleration, the 
drive cannot be restarted after entering Fast Stop until completing deceleration, remove the 
Fast Stop input and cycling the Run command.   
If E2-□□  is set to 44 (During Fast Stop), this terminal will close during Fast Stop.   
If Fast Stop is the action selected for a fault detection, the Fast Stop time set in this parameter 
will be the deceleration time.   
<1>  The setting range  is determined by the  C1-09 (Acc./Dec. Time Unit Selection) setting. When  C1-09  = 0, the 
setting range is 0.00 to 600.00 (second).   
Note: A rapid deceleration will trigger an OVD fault and shut off the drive output causing the motor to  coast. To 
avoid the motor coasting and to ensure the motor stops safely, always set an appropriate time to this parameter.   
  C1-09  Acc./Dec. Time Unit Selection 
Set the time scaling for C1-00 to C1-08. 
Acc./Dec. Time Unit Selection 
0 :    0. 01s 
Sets  the  acceleration  and  deceleration  times  in  0.01  second units.  The  setting range  will  be 
0.00  to  600.00  seconds.  If  600.1  seconds  or  more  is  set  to  any  parameter  among  C1-00  to 
C1-08, C1-09 cannot be set to 0. 
1 :    0. 1s 
Sets the acceleration and deceleration times in 0.1 second units. The setting range will be 0.00 
to 6000.0 seconds. 
  C1-10  Acc./Dec. Time Switch Frequency 
Sets the  frequency level.  The drive will  switch the acceleration and  deceleration  time at this 
level.   
Acc./Dec. Time Switch Frequency 
<1> In control method of PM Closed-Loop Vector Control, the setting range is 0.0 to 100.0%,. The default setting is 
0.0%.   
<2>  The  upper  limit  is  determined  by  the  values  set  to  d1-02  (Maximum  Output  Frequency),  d1-13(Motor2 
Maximum Output Frequency) and L2-00 (Frequency Command Upper Limit) 
 
Note:  This  parameter  will  be  disabled  when  0.0  Hz  (0.0%)  is  set  to  this  parameter.  <1>  The  setting  range  is