211 
 
while attempting to 
perform a fault restart or 
after a momentary power 
loss     
 
3. Check the motor capacity 
· Make sure the motor capacity is 
right for the drive rating.   
4. During a momentary power 
loss or an attempt to reset a fault, 
the alarm is displayed. However, 
there is no need to take any 
action because the fault display 
will disappear shortly   
8.2 Fault Detection 
Table 8.2 Fault Displays, Causes, and Possible Solution 
Output power cable is 
damaged 
Check and replace output power 
cable 
Overvoltage 
(Acceleration, 
Deceleration and 
Constant Speed) 
 
The main circuit DC 
voltage exceeded the 
overvoltage detection 
level 
200V class: 410V 
400 V class: 820 V 
1. Regenerative energy is 
flowing from the motor into 
the drive because the 
deceleration time is too 
short 
2. The motor overshoot the 
speed reference because 
the acceleration time is too 
short   
3. Excessive braking load 
4. Surge voltage entering 
from the drive input power 
5. Motor short-circuited 
Ground fault current 
charges the drive main 
circuit capacitor.   
6. Improper parameter 
settings for Speed Search 
(including Speed Search 
after a fault restart and after 
a momentary power loss)   
7. Drive input voltage is too 
high   
1. Increase the deceleration time 
settings (C1-01, C1-03, C1-05, 
C1-07) 
»Install a braking unit or a 
dynamic braking resistor   
»Set P3-03 (Stall Prevention during 
Deceleration) to 1 
(Enabled)(default is 1) 
2. Confirm if overvoltage alarm 
oVA or oVC was triggered during 
sudden drive acceleration.   
»Increase the acceleration time 
»Use S-curve deceleration and 
acceleration times and increase 
the value set to C2-01 ( S-curve 
at acceleration end )   
3. Install a braking unit or a 
braking resistor 
4. Install a DC reactor 
»Thyristor convertor and phase 
advancing capacitor using the 
same input power supply might 
cause a voltage surge