Figure 6.35 Jog Frequency Command Operation
L2 Frequency Upper / Lower Limit
Sets the upper and lower limits to make sure the motor runs in the range set to prevent
resonance or machinery damage.
L2-00 Frequency Command Upper Limit
Sets the upper limit as a percentage of the maximum output frequency. Even if a frequency
command higher than this level is entered, the drive will run at the limit set to this parameter.
No.
Name
Setting Range
Default
L2-00
Frequency Command Upper Limit
0.0 to 110.0 %
100.0 %
L2-01 Frequency Command Lower Limit
Sets the lower limit as a percentage of the maximum output frequency. Even if a frequency
command lower than this level is entered, the drive will run at the limit set to this parameter.
No.
Name
Setting Range
Default
L2-01
Frequency Command Lower Limit
0.0 to 110.0%
0.0%