107
This gain adjustment depending on the application field, if the load is heavy increase this value,
otherwise reduce this value
No.
Name
Setting Range
Default
C7-00
Proportional Gain
0~100%
Default:30%
6.4 Group L, Frequency Command
L1 Frequency Command
b1-00
Frequency Command
Source 1
Pulse Train Input
RS-485 Commnunication
External I/O Terminal
Terminal A1/A2
L01-00
Frequency Command 1
b1-07
Frequency Command
Source 2
Pulse Train Input
RS-485 Commnunication
External I/O Terminal
Terminal A1/A2
L01-00
Frequency Command 1
Terminal A2
L1-01
L1-02
L1-03
L1-14
L1-15
L1-16
Frequency
Command
= 4
= 3
= 2
= 1
= 0
= 4
= 3
= 2
= 1
= 0
Multi-Function
Input
E1-00 = 4
0
1
Remote
Local
Multi-Step Speed
1
Auxiliary Frequency
Command
Frequency
Command
4~16
Job
Command
Multi Step
Speed 2
Multi Step
Speed 3
1Multi Step
Speed 4
1Multi Step
Speed 15
Multi-Step
Speed 16
Jog Command
Multi-Step Speed
Command
E3-07=3
307E3
Open
Closed
E1-□□= 9
Figure 6.34 Frequency Command Diagram
L1-00 to L1-16 Frequency Command 1 to 16 and Jog Frequency Command
The drive allows the user to switch between up to 16 frequency commands and 1 Jog
frequency command. The drive uses the selected acceleration and deceleration times when
switching between each frequency command.
The Job frequency command overrides frequency command 1 to 16.
No.
Name
Setting Range
Default