or when b1-01 or b1-08 is set to 0. When the operator is reconnected, the display will indicate
that it was disconnected.
No.
Name
Setting Range
Default
o2-05
Operation Selection when Digital Operator is
Disconnected
0,1
0
0 Continue Operation
The operation continues
1 Trigger a Fault
The operation stops and triggers an oPr fault. The motor coasts to stop
o2-06 Operation Direction at Power Up when Using Keypad
Determines the motor rotating direction after the drive power up and the Run command is
entered from the digital operator.
Note: This parameter is provided only in Local mode when b1-01=0 or b1-08 = 0 (Keypad).
No.
Name
Setting Range
Default
o2-06
Operation Direction at Power Up when Using Keypad
0, 1
0
0 : Forward
1 : Reverse
o4 Maintenance Settings
o4-00 Cumulative Operation Time Setting
Sets the initial value by 10 hours to start keeping track of cumulative operation time. The
cumulative operation time can be viewed in U3-00.
Note: A setting of 20 will set the cumulative operation time to 200h and the monitor will display 200h in U3-00.
No.
Name
Setting Range
Default
o4-00
Cumulative Operation Time Setting
0 to 6000 h
0h
o4-01 Cumulative Operation Time Selection
Selects the conditions in which the drive keeps track of the cumulative operation time.
No.
Name
Setting Range
Default
o4-01
Cumulative Operation Time Selection
0, 1
0
0 Time of Power On
Keeps track of time from the power up to power cutoff.
1 Time of Run

Table of Contents