4.2.3 Main Circuit Cable Size and Tightening Torque
Select the cables and crimp terminals according to Table 4.2.2.
1. The recommended cables (copper conductors) are 600 V vinyl-sheathed cables which have
continuous temperature tolerance up to 75°C with ambient temperature tolerance up to 40 °C,
wiring distance up to 100 meters and conditions suitable for on Normal Duty mode.
2. Terminal +1, +2, B1 and B2 are only for connecting DC reactor and braking resistor options.
Do not connect it to other devices.
3. Consider the amount of voltage drop when selecting cable sizes. Increase the cable size
when the voltage drop exceeds 2% of the motor rated voltage. The amount of voltage drop
can be calculated using the following formula:
Line drop voltage (V) = 3 × cable resistance (Ω/km) × cable length (m) × current (A) × 10
-3
Table 4.2.2 Cable Size and Tightening Torque (Three-phase 400 V)
Drive
Rating
Terminal
Asia
USA
Europe & China
Terminal
Screw
Thread
Tightening
Torque
Nm ( lb.in.)
Suggested
Cable Size
mm2
Applicable
Cable Size
mm2
Suggested
Cable Size
AWG, kcmil
Applicable
Cable Size
AWG, kcmil
Suggested
Cable Size
mm2
Applicable
Cable Size
mm2
1.5kW ~
2.2kW
B1,B2,-,R/L1,
S/L2,T/L3,
U/T1,V/T2,W
/T3
1.3
1.3~ 3.3
16
16 ~ 12
1.3
1.3~ 3.3
M4
1.36
3.7kW ~
5.5kW
B1,B2,-,R,S,T,
U,V,W
3.309
3.309~8.368
8
12 ~ 8
3.309
3.309 ~
8.368
M4
1.8 (15.9)
7.5kW ~
11kW
DC1,DC2,B2,-
,
R,S,T,U,V,W
8.3
5.3 ~ 8.3
8
10 ~ 8
8.3
5.3 ~ 8.3
M5
2.26
20