101
determined by the C1-09 (Acc./Dec. Time Unit Selection) setting. When C1-09 = 0, the setting range is 0.00 to
600.00 (second).
C1-11/ C1-12 Jog Frequency Acc. / Dec. Time
C1-11 sets the acceleration time from 0Hz to the Jog frequency command (L1-16). And C1-12
sets the deceleration time from the Jog frequency command (L1-16) to 0Hz.
<1> The setting range changes depending on the C1-09 setting. When C1-09 = 0 (Units of 0.01s), the range will be
0.00s to 600.00s.
C2 S-Curve Characteristics
Sets the S-curve characteristics to reduce the shock to the machinery at start and stop. Sets the
S-curve characteristic time at the start and stop of acceleration and deceleration.
C2- 00 to C2- 03 S-Curve Characteristic at Start/Stop of Acc./Dec.
Sets the S-curve characteristic time in C2-00 to C2-03.
S-Curve Characteristic
at Acc. Start
S-Curve Characteristic
at Acc. End
S-Curve Characteristic
at Dec. Start
S-Curve Characteristic
at Dec. End
S-curve characteristics are illustrated below.