257
4
3
Read register error
6
Write register error
8
Response pocket error
10
Write register error
11.8.2 Slave Response
In the following situations, the slave will ignore the command message sent from the master
and not respond to it.
When a communications error (overrun, framing, parity, or CRC) is detected in the
command message.
The slave address in the command message do not match the slave address in the drive
(Set the slave address for the drive using E6-06 in advance).
The gap between two blocks of a message is greater than 24 bits.
The command message length is incorrect.
Note: When the slave address in the command message is 00H, all slaves perform the write function, but do not
send any response message to the master.