EasyManua.ls Logo

LiteOn EVO 6800 Series - Group E, Multi-Function Terminals; E1 Multi-Function Digital Inputs

LiteOn EVO 6800 Series
261 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
127
6.6 Group E, Multi-Function Terminals
E1 Multi-Function Digital Inputs
E1- 00 to E1- 07 Terminal S1 to S7 Function Selection
Assigns functions to multi-function terminals S1 to S7. Set this parameter according to Table
6.18.
No.
Name
Setting Range
Default
E1-00
Terminal S1 Function
Selection
074 / 100~174
0 : 2-Wire Sequence Control (Forward/Stop)
E1-01
Terminal S2 Function
Selection
074 / 100~174
1: 2-Wire Sequence Control (Forward/Stop)
E1-02
Terminal S3 Function
Selection
074 / 100~174
23 : External Fault
E1-03
Terminal S4 Function
Selection
074 / 100~174
39: Fault Reset
E1-04
Terminal S5 Function
Selection
074 / 100~174
5: Multi-Step Speed Command 1
E1-05
Terminal S6 Function
Selection
074 / 100~174
6: Multi-Step Speed Command 2
E1-06
Terminal S7 Function
Selection
074 / 100~174
9: Jog Frequency
Note1. Digital input terminals if necessary reverse input function, parameter settings can be selected for
its hundreds digit 1 can be realized
EX: Forward / stop selection for the NC mode, the parameter can be set to 100.
Note2. Parameters option contains 223 to 38,select NC modes
Table 6.18
Setting
Functions
Setting
Functions
0
2-Wire Sequence Control
(Forward/Stop)
41
Multi-Function Analog Input Selection
(Terminal A1 and A2)
1
2-Wire Sequence Control
(Reverse/Stop)
42
Retain
2
3-Wire Sequence
43
Retain
3
Local/Remote Selection
44
Retain
4
Command Source 1/2 Selection
45
Communication Mode
5
Multi-Step Speed Command 1
46
PID Disable
6
Multi-Step Speed Command 2
47
PID Integral Reset