information is not written on the motor nameplate. Contact the motor manufacturer for the
information.
Number of Motor Poles Setting
d2-03 is only enabled in Closed-Loop V/F Control and Closed-Loop Vector Control. Enter the
number of motor poles written on the motor nameplate.
Motor Line-To-Line Resistance Setting
d2-04 will be set automatically during Auto-Tuning. However if Auto-Tuning cannot be
performed, contact the motor manufacturer for the test report. Use the line-to-line resistance
listed in the rest report to calculate the line-to-line resistance by the following formula.
· E-type insulation: the resistance value (Ω) listed on the test report at 75°C × 0.92
· B-type insulation: the resistance value (Ω) listed on the test report at 75°C × 0.92
· F-type insulation: the resistance value (Ω) listed on the test report at 115°C × 0.87
Motor Leakage Inductance Setting
d2-05 will be set automatically during Auto-Tuning.
Motor Rotor Resistance and Mutual Inductance Setting
d2-06 and d2-07 will be set automatically during rotational Auto-Tuning.
Set the Motor Mechanical Loss