126 
 
information is not written on the motor nameplate. Contact the motor manufacturer for the 
information.   
□ Number of Motor Poles Setting 
d2-03 is only enabled in Closed-Loop V/F Control and Closed-Loop Vector Control. Enter the 
number of motor poles written on the motor nameplate.   
□ Motor Line-To-Line Resistance Setting 
d2-04  will  be  set  automatically  during  Auto-Tuning.  However  if  Auto-Tuning  cannot  be 
performed, contact the motor manufacturer for the test report. Use the line-to-line resistance 
listed in the rest report to calculate the line-to-line resistance by the following formula.   
·  E-type insulation: the resistance value (Ω) listed on the test report at 75°C  ×  0.92 
·  B-type insulation: the resistance value (Ω) listed on the test report at 75°C  ×  0.92 
·  F-type insulation: the resistance value (Ω) listed on the test report at 115°C  ×  0.87 
□ Motor Leakage Inductance Setting 
d2-05 will be set automatically during Auto-Tuning. 
□ Motor Rotor Resistance and Mutual Inductance Setting 
d2-06 and d2-07 will be set automatically during rotational Auto-Tuning. 
□    Set the Motor Mechanical Loss