125
Sets the motor rotor resistance. This will be set automatically during Auto-Tuning.
No.
Name
Setting Range
Default
d2-06
Motor Rotor Resistance
0.000 to 65.000 Ω
<1>
Determined by o2-03,
A1-06
d2- 07 Motor Mutual Inductance
Sets the motor mutual inductance. This will be set automatically during Auto-Tuning.
No.
Name
Setting Range
Default
d2-07
Motor Mutual Inductance
0.0 to 6500.0 mH
Determined by o2-03,
A1-06
d2- 08 Retain
d2- 09 Retain
d2- 10 Motor Rated Capacity
Sets the motor rated capacity in units of 0.01kW. This will be set automatically during
Auto-Tuning.
No.
Name
Setting Range
Default
d2-10
Motor Rated Capacity
0.00 to 650.00 kW
Determined by o2-03
Note: If the maximum motor capacity the drive can run is less than 300kW, it will be displayed in units of 0.01kW. If
the maximum motor capacity the drive can run is more than 300kW, it will be displayed in units of 0.1kW.The
maximum motor capacity the drive can run is determined by A1-06 (ND/HD Mode). Refer to Ch 2.4 on page 15.
Motor Parameters Manual Setting
Use the information listed on the motor test report and follow the instructions below.
Motor Rated Current Setting
Enter the rated current written on the motor nameplate to d2-00.
Motor Rated Slip Setting
Use the rated speed written on the motor nameplate to calculate the motor rated slip and set
to d2-01.
Motor rated slip = motor rated frequency [Hz]- rated speed ( min
-1
)×number of motor poles /
120
Motor No-Load Current Setting
Sets the motor no-load current when running at no-load voltage and rated frequency. This