66
150 %
100 %
Overload
Rated Load
100 %
0
Motor Speed
120 %
100 %
Overload
Rated Load
100 %
0
Motor Speed
Applications which require a high
overload tolerance at start, during
acceleration or deceleration such as
extruders and cranes.
Applications which do not require a
high overload tolerance such as fans
and pumps.
Stall Prevention during
Acceleration (P3-01)
Stall Prevention during
Run (P3-06)
Note: Changing the duty mode automatically changes the maximum motor rating that the drive can run, defaults of
d2-□□ and parameters related to the motor rating.
A2 User-Defined Parameters
A2- 00 to A2- 31 User-Defined Parameters 1 to 32
Selects up to 32 parameters and assigns them to parameter A2-00 to A2-31.
User-Defined Parameters 1 to 32
■ Recently Edited Parameter Save
Saved parameters can be viewed in User-Defined Parameter Access. To assign specific
parameters to A2-00 to A2-31, set parameter A1-01 to 2. The saved parameters A2-00 to
A2-31 can only be viewed if A1-01 is set to 1.
A2-32 User-Defined Parameter Automatic Save
Enables or disables the automatic save for A2-16 to A2-31.
User-Defined Parameter Automatic Save
0 : Enabled
Sets A2-32 to 0 to save the parameter manually.