EasyManua.ls Logo

LiteOn EVO 6800 Series - Terminal am Voltage;Current Output Selection

LiteOn EVO 6800 Series
261 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
4.4.3 Terminal AM Voltage/Current Output Selection
Select voltage or current output type for terminal AM
To select voltage as the output type, set DIP switch AM to V and set parameter E4-04 to 0
(0 to 10 V) .
To select current as the output type, set DIP switch AM to I and set parameter E4-04 to 1 (0
to 20 mA) or 2 (4 to 20 mA).
Figure 4.4.3 DIP Switch AM
Table 4.4.3 DIP Switch AM Setting (Terminal AM)
Setting
Description
V
Voltage output (0 to 10 V)
I
Current output (4 to 20 mA or 0 to 20 mA) (default)
Table 4.4.4 Parameter 4-04
No
Parameter Name
Description
Setting
Range
Default
E4-04
Terminal AM Signal Level
Selection
Selects the signal level for
terminal AM
0 : 0 to 10 V
1 : 0 to 20 mA
2 : 4 to 20 mA
0, 1, 2
2

Table of Contents

Other manuals for LiteOn EVO 6800 Series

Related product manuals