195 
 
CAUTION! An incorrect o2- 03 setting may cause the drive performance to suffer and drive damage.     
Determined by 
drive capacity 
 
Rating (kW) 
(200V series) 
Rating (kW) 
(200V series) 
Rating (kW) 
(400V Series) 
Rating (kW) 
(400V Series) 
 
  o2-04  ENTER Key Function During Frequency Command Setting 
Determines whether the  ENTER  key is required  to  be  pressed  after changing the  frequency 
command using the keypad in Local mode.   
ENTER Key Function During Frequency Command 
Setting 
0 : ENTER Key Required 
The ENTER key is required to be pressed to trigger the frequency command.     
1 : ENTER Key Not Required 
When entering a frequency command, the output frequency changes immediately by UP or 
DOWN key without pressing ENTER. The frequency command will be saved 5 seconds after it is 
changed by pressing the UP or DOWN key.   
  o2- 05  Operation Selection when Digital Operator is Disconnected 
Determines whether the drive will stop when the digital operator is removed in LOCAL mode