Note: In PM Open-Loop  Vector  ControlP (A1-02=5), make  sure the cable connecting the drive and  motor  is less 
than 100 meters.   
  C6-01/ C6-02/ C6-03  Maximum / Minimum Carrier Frequency / Carrier Frequency 
Proportional Gain  
Set  0  to  parameter  C6-00  to  enable  this  setting.  Sets  the  maximum  and  minimum  carrier 
frequency in V/F Control that the drive will adjust carrier  frequency according to  the output 
frequency.     
Maximum Carrier Frequency 
Minimum Carrier Frequency 
Carrier Frequency Proportional Gain     
<1> This setting is only enabled when C6-00=0.   
□ Setting a Fixed Carrier Frequency   
C6-01 can be adjusted within the setting range when C6-00 is set to 0.   
Set the same value in C6-01 and C6-02 in control methods other than V/F Control.     
□ Setting a Variable Carrier Frequency (Only for V/F Control) 
In V/F Control, the carrier frequency can be set up to change linearly with the output frequency 
by setting C6-01, C6-02 and C6-03 as shown in Figure 6.33. 
 
Carrier Frequency
C6-01
Output Frequency 
╳ C6-03
Output 
Frequency
d1-02
Maximum Output Frequency
 
Figure 6.33 Carrier Frequency Changes Based on Output Frequency 
Note:   
1. When C6-03>27 and C6-01<  C6-02 , the carrier frequency will be fixed to the value set to C6-01. 
2. When C6-03<7, C6-02 is disabled and the carrier frequency will be fixed to the value set to C6-01.   
  C7-00    Proportional Gain