120
<1> This will not be reset by A1-03 (Reset).
<2> In Vector Control, d1-01 =F.
□ Preset V/F Pattern Selection (Setting Value 0 to E)
The preset V/F patterns are listed in Table 6.13. Select the appropriate V/F pattern and set to
this parameter. d1-02 to d1-11 cannot be edited.
Note:
1. An improper V/F could cause motor undertorque or increased current because of overexcitation.
2. d1-01 will not be reset by A1-03 (Reset).
Table 6.13 V/F Pattern Selection
For general purpose applications such as
conveyors. The torque remains constant
regardless of the speed.
For applications such as fans, pumps and
other derated loads.
50 Hz, mid starting torque
· Long wiring between the drive and motor
(more than 150 m)
· Large starting torque is required such as
elevators.
· AC reactor is installed on the drive output
side
50 Hz, high starting torque
60 Hz, mid starting torque
60 Hz, high starting torque
Constant output voltage when running at
60 Hz and above.
The characteristics of the V/F patterns are illustrated in the following table. The table shows the
V/F patterns for 200V. The voltage will be doubled for 400V.